Monday, January 26, 2026

VENTILATION OUTAGE - NORTH RAL - JANUARY 29TH AND 30TH FROM 6:00AM TO 8:00AM

TO ALL IN NORTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the listed rooms in North RAL on Thursday, January 29th and Friday, January 30th from 6:00AM to 8:00AM. This outage is needed to change filters on the supply and exhaust fans serving those rooms. During the outage, there will be no supply or exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outages are listed below:

Outage Request Number: 74093

Outage Time : 2026/01/29 06:00 until 2026/01/30 08:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : Rooms,RAL : DOA-02=10,11,11A,12,14,17,19,19A,19B,112,112A,216,216A,219,221,304,412,412B,412C,412CI,

DOA-03=197,199,294A,294B,295,296,299,390,390A,390C,392,392A,490,491,493,494,494B,495,496,497,498 & 498A

Building Services affected : Supply Air,Make Up Air, Fume Hood Exhaust,Cabinet Exhaust & General Lab Exhaust

Building Occupants Effect : Lack of all listed above.

Ventilation Fan No. : DOA-2 & DOA-3 & Supply & Exhaust Fans serving these units.

Ventilation Area. : see rooms below

Comments : 1-29-2026 & 1-30-2026 (Daily) Not Continuous. These units operate in tandem and both must be shut down to service the filters. Please cap all chemicals and close fume hood sashes.

Reason : To Change Filters on the Exhaust side of these units and inspect DOAs.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/


Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

VENTILATION OUTAGE - SOUTH RAL - JANUARY 28TH FROM 6:00AM TO 10:00AM

TO ALL IN SOUTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the listed labs in South RAL on Wednesday, January 28th from 6:00AM to 10:00AM. This outage is needed to change filters on the exhaust fans serving those rooms. During the outage, there will be no exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outage are listed below:

Outage Request Number: 74091

Outage Time : 2026/01/28 06:00 until 2026/01/28 10:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : Rooms 272,273,274,275,276,277,278,279,373,374,375,376,379

Building Services affected : Supply Air & Fume Hood exhaust Air will be off.

Building Occupants Effect : Lack of supply & exhaust air in areas listed.

Ventilation Fan No. : HE-1,Hartwig Labs, Supply and Fume Hood Exhaust

Ventilation Area. : Rooms 272,273,274,275,276,277,278,279,373,374,375,376,379

Comments : Please cap all chemicals and close fume hood sashes.

Reason : To Change Filters in Fume Hood Exhaust System and inspect unit.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/

Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

LAB VACUUM OUTAGE - CLSL-A THIRD FLOOR - JANUARY 27TH FROM 7:00AM TO 3:30PM

LSOs/Faculty,

F&S will be conducting a LAB VACUUM OUTAGE affecting the 3rd floor of CLSL-A on Tuesday, January 27th from 7:00AM to 3:30PM. This outage is needed to repipe a section of the vacuum line in room A327. During the outage, all labs on the 3rd floor will be without lab vacuum at both the fume hood turrets and bench turrets. To prepare for the outage, the occupants of A327 will need to clear the area around the sink and affected fume hood of all flammable materials and other obstructions. Further details about the outage are listed below:

Outage Request Number: 74134

Outage Time : 2026/01/27 07:00 until 2026/01/27 15:30

Outage Type : VACUUM SYSTEM (OTHER)

Building : 0070 - CHEMICAL & LIFE SCIENCES LABORATORY

Building Sections affected : 3rd floor

Building Services affected : Lab vacuum

Building Occupants Effect : No vacuum in fume hoods or table mounted turrets

Comments : The area around the sink and around the fume hood needs all flammables removed and area clear of obstructions.

Reason : LAB A327. NEED TO THE REPIPE A SECTION OF THE VACUUM LINE.... VACUUM PORT IN FUME HOOD A327-2 ON THE RIGHT SIDE IS NOT WORKING. BE THE NORTH EAST FUME HOOD

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/


Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

Thursday, January 22, 2026

VENTILATION OUTAGE - SOUTH RAL - JANUARY 23RD FROM 6:00AM TO 10:00AM

TO ALL IN SOUTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the west wing of the 2nd-4th floors of South RAL on Friday, January 23rd  from 6:00AM to 10:00AM. This outage is needed to change filters on the DOA-102 fans. During the outage, there will be reduced supply air and NO fume hood/cabinet exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outage are listed below:

Outage Request Number: 74089

Outage Time : 2026/01/23 06:00 until 2026/01/23 10:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : RAL South, Rooms; 236,237,240,241,244,245,245b,247,248,249,252,253,254,256,257,260,260c,261,261b,263,336,338,340,341,343,344,345,345b,347,348,349,352,352b,353,354,354b,356,357,360,361,361b,363,370,436,437,440,441,443,444,445,448,449,452,452b,453,454,454b,456,457,460,461,461b,463

Building Services affected : There will be Reduced supply air and NO exhaust air to the Fume Hoods on the North walls of labs.

Building Occupants Effect : Reduced conditioned air and NO fume hood or cabinet exhaust for North fume hoods.

Ventilation Fan No. : DOA-102 Supply and Exhaust Fans

Ventilation Area. : see rooms below

Comments : Please CAP all chemicals and CLOSE all sashes to fume hoods.

Reason : We are changing the filters on the exhaust side of this system.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/

Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

Wednesday, January 21, 2026

CHILLED WATER OUTAGE - RAL - JANUARY 22ND FROM 7:00AM TO 3:00PM

TO ALL IN RAL:

F&S will be conducting a CHILLED WATER OUTAGE affecting RAL on Thursday, January 22nd from 7:00AM to 3:00PM. This outage is needed to clean the building chilled water strainer. During the outage, occupants may notice warmer than usual temperatures. The outage will also shut down the cold room in 160 RAL so make sure to relocate any temperature sensitive materials to a different storage location until the outage is complete. Further details about the outage are listed below:

Outage Request Number: 74127

Outage Time : 2026/01/22 07:00 until 2026/01/22 15:00

Outage Type : CHILLED WATER

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : Entire Building

Building Services affected : Chilled water

Building Occupants Effect : Warmer than normal temps / Outside air should cool building / Cold room 160 will be down and reset after outage

Comments : null

Work order # : 11275552 CLEAN CHILL WATER STRAINERS ANNUAL FIXED REFRIGERATION

Reason : Cleaning building chilled water strainer

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/

Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

SMOKE ALARM, LP STEAM, HEAT, DOMESTIC HOT WATER OUTAGE - DAVENPORT HALL - JANUARY 22ND FROM 4:00AM TO 2:30PM

TO ALL IN DAVENPORT:

F&S will be conducting an outage affecting Davenport Hall on Thursday, January 22nd from 4:00AM to 2:30PM. This outage is needed to repair a leaking flange on a low pressure steam line. During the outage, the low pressure steam, heat, and domestic hot water systems will be turned off so there will not be any hot water available and the building may be cooler than usual. Further details about the outage are listed below:

Outage Request Number: 74131

Outage Time : 2026/01/22 04:00 until 2026/01/22 14:30

Outage Type : SMOKE ALARM, LP STEAM, HEAT, DOMESTIC HOT WATER (OTHER)

Building : 0001 - DAVENPORT HALL

Building Sections affected : Entire

Building Services affected : smoke alarm, LP steam, heat, domestic hot water

Building Occupants Effect : may be cooler than normal, no domestic hot water

Comments : we will need Steam Distribution assistance, we would like it shut off at 4:00am so it can cool. smoke alarm off at 6:00am

Work order # : 11247623 SOUTH HALLWAY UNDER THE STAIRS IN BASEMENT - HALF WAY DOWN TO THE EAST OF THE BASEMENT THERE IS A LOW PRESSURE STEAM LEAK; FLANGE GASKET LEAKING. LES IS AWARE.

Reason : Fix leaking flange

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/


Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

VENTILATION OUTAGE - SOUTH RAL - JANUARY 27TH FROM 6:00AM TO 10:00AM

TO ALL IN SOUTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the listed rooms in South RAL on Tuesday, January 27th from 6:00AM to 10:00AM. This outage is needed to change filters on the EF-104A, EF-104B, and EF-104C fans. During the outage, there will be no exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outage are listed below:

Outage Request Number: 74092

Outage Time : 2026/01/27 06:00 until 2026/01/27 10:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : Rooms; 37A,37B,45,45B,47,47B,49,49B,53,53B,53C,55,55B,57,57B,72,75,76,77,79,79C,145,155,157,172,173,176,177,179,472,473,476,477,478

Building Services affected : Exhaust Air to these Spaces.

Building Occupants Effect : NO exhaust to the spaces listed above.

Ventilation Fan No. : (Old)RAC-104, ERC-2,EF-104A, EF-104B & EF-104C

Ventilation Area. : see rooms below

Comments : Please cap all chemicals and close fume hood sashes during this outage.

Reason : To change filters serving these fans.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/


Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

VENTILATION OUTAGE - SOUTH RAL - JANUARY 22ND FROM 6:00AM TO 10:00AM

TO ALL IN SOUTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the west wing of the 2nd-4th floors of South RAL on Thursday, January 22nd from 6:00AM to 10:00AM. This outage is needed to change filters on the DOA-101 fans. During the outage, there will be reduced supply air and NO fume hood/cabinet exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outage are listed below:

Outage Request Number: 74088

Outage Time : 2026/01/22 06:00 until 2026/01/22 10:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : RAL South, Rooms; 238,239,242,243,246,247,250,251,254,255,258,259,263,338,339,342,343,346,350,351,354,354b,355,358,359,361b,363,370,438,439,442,443,446,447,450,451,454,454b,455,458,459,461b,463

Building Services affected : There will be Reduced supply air and NO exhaust air to the Fume Hoods on the South walls of labs.

Building Occupants Effect : Reduced conditioned air and NO fume hood or cabinet exhaust for South fume hoods.

Ventilation Fan No. : DOA-101 Supply and Exhaust Fans

Ventilation Area. : see rooms below

Comments : Please CAP all chemicals and CLOSE all sashes to fume hoods.

Reason : We are changing the filters on the exhaust side of this system.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/


Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

Friday, January 16, 2026

VENTILATION OUTAGE - SOUTH RAL - JANUARY 20TH FROM 6:00AM TO 10:00AM

TO ALL IN SOUTH RAL:

F&S will be conducting a VENTILATION OUTAGE affecting the listed rooms in South RAL on Tuesday, January 20th from 6:00AM to 10:00AM. This outage is needed to change filters on the EF-103A, EF-103B, and EF-103C fans. During the outage, there will be no exhaust air available in the affected rooms so no research should be taking place. To prepare for the outage, please make sure that all chemical/waste containers are sealed and that fume hood sashes are closed. Further details about the outage are listed below:

Outage Request Number: 74090

Outage Time : 2026/01/20 06:00 until 2026/01/20 10:00

Outage Type : VENTILATION

Building : 0116 - ROGER ADAMS LABORATORY

Building Sections affected : Rooms; 35,36,37E,37D,37C,40,41,42,42B,43,44,46,50,50B,56,58,58B,60,60C,61,63,63C,135A,136,137,140,140B,142,143,146,148,150,154,156,160,160D,161,161B,163,235A,335A & 435A

Building Services affected : Exhaust air to these spaces.

Building Occupants Effect : NO exhaust to the spaces listed above.

Ventilation Fan No. : (Old RAC103)-ERC-1 -EF103A,EF-103B & EF-103C

Ventilation Area. : see rooms below

Comments : Please cap all chemicals and close fume hood sashes during this outage.

Reason : To change filters serving these fans.

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/

Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences

16 Roger Adams Lab

217-300-6618

sbrownfi@illinois.edu

https://scs.illinois.edu/

https://besafe.illinois.edu/

 

Monday, January 12, 2026

LOW PRESSURE STEAM OUTAGE - NOYES LAB - JANUARY 13TH FROM 2:30AM TO 2:30PM

TO ALL IN NOYES:

F&S will be conducting a LOW PRESSURE STEAM OUTAGE affecting Noyes Lab on Tuesday, January 13th from 2:30AM to 2:30PM. This outage is needed to fix a cracked radiator. During the outage, building occupants may notice cooler than usual temperatures. Further details about the outage are listed below:

Outage Request Number: 74097

Outage Time : 2026/01/13 02:30 until 2026/01/13 14:30

Outage Type : LOW PRESSURE STEAM

Building : 0012 - NOYES LABORATORY OF CHEMISTRY

Building Sections affected : entire

Building Services affected : perimeter steam heat

Building Occupants Effect : May be cooler than normal

Comments : we will need Steam Distribution assistance

Work order # : 11290216 ROOM 114 STEAM RADIATOR CRACKED AND LEAKING, LES IS AWARE

Reason : Fix radiator 11290216

If you have any further questions or concerns, please do not hesitate to email the SCS Facilities and Safety team at scs-facilities@illinois.edu. This information will also be available for viewing on the SCS Building Outages/Important Notices blog: https://buildingoutages.scs.illinois.edu/

Shane Brownfield, CCHO

Safety and Inventory Supervisor– School of Chemical Sciences